PRODUCTION SERIES

Class I, Division 1 & Division 2 Extraction Booths developed to maximize output

Footprints

Production Series: Model 170

Interior Square Feet

Interior Dimensions

Exterior Dimensions

Configurations

Available Extensions

170 Square Feet

14’0” W x 12’2” L x 9’1.5” H

14' 3" W x 13' 8" L x 9' 4.5" H

CID1 & CID2

Degassing Cabinet,

Height Extension Package

Production Series: Model 265

Interior Square Feet

Interior Dimensions

Exterior Dimensions

Configurations

Available Extensions

265 Square Feet

14' W x 19'1" L x 9'1.5" H

14'3" W x 20'4" L x 9'4.5" H

CID1 & CID2

Degassing Cabinet,

Height Extension Package

Production Series: Model 355

Interior Square Feet

Interior Dimensions

Exterior Dimensions

Configurations

Available Extensions

355 Square Feet

14’0”W x 25’6”L x 9’1.5”H

14’3”W x 27’0”L x 9’4.5”H

CID1 & CID2

Degassing Cabinet, Height Extension Package

 

Production Series Standard Package

  • 9'1.5" or 10'1.5" Interior Height

  • 14'3" Exterior Width

  • Minimum Base Air Flow Rate: 1500 CFM

  • Minimum Purge Air Flow Rate: 3000 CFM

  • Explosion-proof, Class I, Division 1, 2-tube Interior LED Light Fixtures

  • Fire-rated door and exit hardware

  • Extra-long life, flammable gas infrared sensor

  • Supply and Exhaust Ventilation Assemblies - Includes exhaust and supply fans built with explosion-proof construction and CID1 motor assembly

  • Exterior CID2 remote operator switch

  • Interior CID1 manual purge button

  • 110W Uninterrupted Power Supply (UPS) - upgraded UPS options available to back up the entire booth system

  • 36” wide personnel door sealed by a rubber compression gasket

  • Cross-capture ventilation

  • A fire-rated panic bar for emergency exiting

  • Professional engineer peer-reviewed design

  • UL Certification *Not available for booth configurations

  • Exterior CID2 tri-color light alarm and exterior warning siren / Light alarm and siren set to go off at 10% and 25% of LEL, respectively

  • Fully compliant with applicable OSHA, NFPA, NEC regulations

  • Access Panel with Utility Penetration Plate to easily run heating, cooling, and air lines to approved extraction equipment located inside of the HAL Booth

Compliance

UL CERTIFIED

PEER-REVIEWED

The First and Only UL Certified Extraction Booths

 

​The use of flammable and pressurized solvents can create dangerous conditions for workers and buildings. HAL Extraction has worked with Underwriters Laboratories (UL) to develop and certify the first equipment for use in the plant oil extraction industry.

HAL Extraction Product Lines Achieves PSI Technical Report Certification in 50 States

 

HAL Extraction Booths and Hoods have been Peer-reviewed by Pressure Safety Inspectors (PSI)

Configurations

Classic Series CID1 Booths

Classic Series CID2 Booths

HAL Extraction Class 1, Division 1 Extraction Booths are designed for use with class IA flammable liquids in hydrocarbon extraction methods. 

HAL Extraction Class 1, Division 2 Extraction Booths are designed for use with class IB flammable liquids in ethanol extraction methods. 

Booth Extension Packages

Height Extension Package

  • 10' Height option available

  • 10' 1.5" interior height

Degassing Cabinet

HAL's Degassing Cabinet is an independent space that works in conjunction with the HAL Extraction Booth during the plant oil extraction process.

 

It was created to safely off-gas used plant material still wet with solvents in a contained area, without compromising the safety of your CID1 space. 

10 ft

170P.png
20DGS_nobackground.png